35KV Heat Shrinkable Joint
35KV Heat Shrinkable Joint
Supplier Info
[China Supplier]
Contact Person : Mr. shen Feng
Tel : 0086-512-66651289
Fax : 0086-512-66651088
Product Detail
1.Operating Temperature:-40 degree - 110 degree; 2.Shrink Temperature:90 degree; 3.Waterproof, RoHS compliant.

Product Introduction:

35KV heat shrinkable joints are designed for 1 and 3-core XLPE power cables. The whole set contains heat shrinkable outer and inner insulation tubes,stress control tubes, sealing tubes,protective tubes,self adhesive tape and voil filler.Its unique patented water-proof design ensures the higher security of cable accessories.

Its high permittivity material endows it unique stress control system. And with compact design and few components, this product is easy to install, minimal waste for disposal. Fast, consistent installation means lower installing costs. Installation environment: use of torch adds flexibility to cable preparation in any climate. It also has high reliability. Heat-activated seals ensure maximum protection against moisture ingress. Lightweight construction requires no additional support. UV resistant, non-tracking outer tube for long life, even under adverse conditions. It also has excellent mechanical robustness.

 Technical Data:

PROPERTY

TEST CONDITION AND TEQUIREMENT 

RESULTS

AC withstand for 1 min.(dry withstand, for indoor termination)

No breakdown and flashover shall occur at 105kV, 1min

No breakdown and flashover occurred on the combi.sample at 105kV, 1min

Partial discharge

39kV, ≤10PC

39kV, ≤10PC

Load cycle

Heating for 5h, cooling for 3h. Conductor's temperature is 95, 3 cycles

Conductor's temperature is 95. Results refer to the following test

Impulse voltage withstand 1.2/50us±10times

10 positiVe and 10 negative impulses at 250kV, flashover 1 time is allowed but not including total testing times

No breakdown of the combi.sample occurred at 250kV

DC voltage withstand negative 15 min.

No breakdown and flashover shall occur at 156kV

No breakdown and flashover occurred on the combi.sample at 156kV, 15min

AC voltage withstand, 4h

No breakdown and flashover shall occur at 104kV, 4h

No breakdown and flashover occurred on the combi.sample at 104kV, 4h

Oil-seal up test

Heating for 24h, cooling for 24h. Conductor's temperature is 65, oil pressure: 100MPA

No leaking, no seeping

(Only for Paper insulated cables)

  

35KV Heat Shrinkable Joint