Main technical parameters:
No. | Designation of parameter | Unit | Data of parameter | ||
1 | Rated voltage | kV | 40.5 | ||
2 | Rated isolate lever | 1minpower frequency Withstand voltage | Dry test | kV | 95 |
Wet test | 80 | ||||
Rated lightning impulse withstand voltage(Peak)) | 185 | ||||
3 | Rated current | A | 1250 1600 2000 | ||
4 | Rated short circuit breaking current | kA | 20 25 31.5 | ||
5 | Rated operating sequence |
| opening-0.3s-closing opening-180s-closing opening | ||
6 | Breaking times at rated short circuit breaking current | times | 20 | ||
7 | Rated short circuit making current(peak) | kA | 50 63 80 | ||
8 | Rated peak withstanding current | ||||
9 | Rated short time withstanding current | 20 25 31.5 | |||
10 | Rated short circuit duration time | s | 4 | ||
11 | full breaking current | ms | ≤80 | ||
12 | mechanical life | times | 10000 | ||
13 | Wear thickness allows of Static and dynamic contact | mm | 3 | ||
14 | Weight | kg | 1000 |
mechanical characteristics
No. | Designation of parameter | Unit | Data of parameter |
1 | Contact travel | mm | 23±2 |
2 | Contacting travel | 6±2 | |
3 | Average opening speed | m/s | 1.4~1.7 |
4 | Average closing speed | 0.4~0.7 | |
5 | Bounce time of contact closing | ms | ≤5 |
6 | Three phase asynchroneity (Closing/Opening) | ≤2 | |
7 | Closing time | ms | ≤150 |
8 | Opening time | ≤70 | |
9 | DC resistance for per phase circuit | µΩ | ≤100(not include CT) |
10 | distance between phase center | mm | 71 0/750 |
1, Closing coil(CT19BW mechanism)
Rated service voltage(V) | ~110 | ~220 | -110 | -220 |
Rated service current(A) | 2.72 | 2.5 | 2.34 | 1.16 |
2, Opening coil(CT19BWmechanism)
Rated service voltage(V) | ~110 | ~220 | -110 | -220 |
Rated service current(A) | 2.72 | 2.5 | 2.34 | 1.16 |
40.5KV(33KV & 35KV) Vacuum circuit breaker for outdoor