1.Once Seal-Exhaust Technique 2.Free painting technology 3.316L Stainless steel, easy-welding and environmental friendly

Main Technical Data 

Rated voltage                                            kv40.5
Rated current                                            A1600/2000
Rated frequency                                         Hz50
Rated short-time power frequency withstand voltage(1min)     kv95
Rated lighting impulse withstand voltage                     kv185
Rated short-circuit breaking current                         kA25/31.5
Rated short-circuit making current(peak)                    kA63/80
Rated operations of short-circuit breaking current interruption   times20
Rated single capacitor bank breaking current                  A400
Rated short-time withstand current                         kA25/31.5
Rated peak withstand current                               kA63/80
Rated duration of short-circuit                              s4
Mechanical life                                           times10000
Contact closing force due to bellows and atmosphere          N250±50
Counterforce at rated contact stroke                          N330±60
Circuit resistance at rated contact force                      μΩ≤25
Shelf life                                                  years20
Contact erosion limit                                       mm3
Weight of moving parts                                                                             kg≤4
Mechanical Data Required For Matched Vacuum Switchgear                                             
Rated contact stroke                                      mm22±2
Average opening speed                                   m/s1.6±0.2
Average closing speed                                    m/s0.75±0.2
Added contact force                                       N3100±200
Contact bouncing duration at closing operation                ms≤2
Contact bouncing bank amplitude of opening operation         ms≤4
Three-pole simultaneity                                     ms≤2

Note:Rated characteristics can be customised on requirment