Application
Lower volatge MCC
Integrated process and electrical control
6 modules
main module, current measurement module (CT module), display module, extended digital module, extended analog module,and power supply module.
9 standard protection
start overtime overload overcurrentphase failurecurrent unbalanceearth faultshort circuit underload external fault overvoltage8 optional protection
OvervoltageUndervoltagePhase sequence (only for PMAC801)Under powerEEx e overloadTemperature and analog input (only for PMAC801) Leakage currentTechnical Parameters
Rated voltage of Motor: AC 380V or 660V. Direct connect to PMAC801.
Rated current:
Rated current of motor | Rated current of PMAC801 |
0.5A~2A | 2A |
1.6A~6.3A | 6.3A |
6.3A~25A | 25A |
25A~100A | 100A |
100A~250A | 250A |
250A~500A | 500 A |
500A~820A | 820A |
Note: Users can choose proper type of PMAC801 for motors according to the form above.
Power supply: 85~265V AC or DC.
Type of digital input: PMAC801 provides internal 30VDC power supply for digital input circuit.
Output capacity of control relay:250V/16A, 380V/2A, 110VDC/0.5A
Output capacity of signal relay: 250VAC/5A
Note: PMAC801 has 5 relays, the front 3 are control relays, and the others are signal relays.
Range & Accuracy
Item | Range | Precision | Item | Range | Precision |
Current | 10%~200% Ie | ±1% | Power factor | 0~1 | ±1% |
200%~800% Ie | ±3% | ||||
Leakage current | 10%~100% In | ±1% | Active power | 0~600.0KW | ±2% |
PTC/NTC | 10R~10K | ±5% | Active energy | 99,999,999.9kWh | ±5% |
Voltage | 50%~150%Ue | ±1% | Analog output | 4mA~20mADC | ±2% |
Frequency | 45HZ~65HZ | ±1% | Analog input | 4mA~20mADC | ±2% |
EMC
Electrostatic discharge | EN 61000-4-2, Level 3 |
Electromagnetic field immunity | EN 61000-4-3, Level 3 |
Fast transient/burst immunity | EN 61000-4-4, Level 4 |
Surge immunity | EN 61000-4-5, Level 3 |
Conducted Emission | EN 55022, Class B |
Radiated Emission | EN 55022, Class B |
Environmental Conditions
Ambient temperature of work | -10~+55°C |
Ambient temperature of storage | -25~+70°C |
Humidity | ≤85% |
PMAC801 motor protection circuit breaker