outdoor Hight vacuum circuit breaker Ambient temperature -40 tem. ~ +40 tem. The elevation does not surpass 2000mm

outdoor vacuum circuit breaker

outdoors high vacuum circuit breaker

 Outline

SC40301 - the 12G/T630 - 12.5/16/20 outdoors high vacuum circuit breaker is the three phase ac outdoors high-voltage switch equipment, mainly uses in the 12KV rank, nominal current 630A, the nominal frequency 50HZ agricultural net, the city net, the mine, the railroad, the harbor electrical power distribution system, specially is suitable for the outdoors overhead line, the analysis and synthesis load current, the excess current, the short-circuit current, to electrical network perform handover and protection.

This product is suitable for the below working condition:

A. Ambient temperature -40 °C ~ +40 °C ; B. The elevation does not surpass 2000mm, above 2000mm and the user consultation; C. The wind pressure does not surpass 700Pa (to be equal to wind speed 34m/s); D. The relative humidity date mean value is not bigger than 95%, the monthly mean value is not bigger than 90% e. Air contamination degree III level; F. The surrounding air should not receive the caustic gas or the ignitable gas and so on the obvious pollution; G. Non- regular strenuous exercise; H. Should conform to the GB655386 related use situation requirement as the insulation medium silica gel.

  Main technical parameter

3.1 Fixed parameter

Serial number

Project

Unit

Paramete

1

rated voltage

KV

12

2

nominal currents

A

630

3

Nominal frequency

HZ

50

4

Labor frequency durable voltage

KV

42/48

5

lightning surges voltage (peak value)

KV

75/85

6

The rating short-circuits the drop-out current

KA

6.3

12.5

16

20

7

The rating short-circuits the pass to gather the electric current (peak value)

KA

16

31.5

40

50

8

Fixed short-time durable electric current

KA

6.3

12.5

16

20

9

Fixed peak value durable electric current

KA

16

31.5

40

50

10

Fixed operation sequence

 

 0.3S  180

11

The rating short-circuit current opens breaks the number of times

sequence

30

12

Mechanical life

sequence

10000

13

Moves contact permission attrition accumulation thickness

mm

3

4

14

The fixed operation voltage matches the CT spring to hold the drive mechanism

Gathers

floodgate coil

V

Direct current or exchange 220V

Minute floodgate coil

15

Has flowed the trip coil fixed operating current

A

5

16

Current transformer one, secondary current ratio

 

100/5.200/5.300/5.400/5.630/5

17

Stored energy electrical machinery

The guest decides the voltage

V

Direct current or exchange 220V

Power

W

≤ 200

18

Weight

Kg

150

3.2 Mechanical parameter

Serial number

Project

Unit

Paramete

1

1 contact starts is apart from

mm

11±1

2

contacts travelling schedules

mm

3±0.5

3

evenly to divide equally the floodgate speed

m/s

1±0.2

4

Average Gathers floodgate speed

m/s

0.8±0.2

5

Gathers floodgate bounces the time

ms

≤3

6

Three-phase minute floodgate same time

ms

≤2

7

Three-phase Gathers floodgate same time

ms

≤3

8

Gathers floodgate time

ms

40-60

9

Minute floodgate time

ms

30-50

10

Each extremely main return route resistance

ms

≤200

11

Alternates with the center distance

 

220±1.5

12

Gathers floodgate condition contact spring length

mm

25.5

3.3 Isolator engineering data

Serial number

Project

Unit

Paramete

1

Rated voltage

KV

12

2

Nominal current

A

630

3

4s thermally stable electric current (has effect value)

KA

20

4

Moves the steady state current (peak value)

KA

50

5

1.2/50 mu s full wave striking potential (peak value)

KV

Relatively 75 Fracture 85

6

1min labor frequency pressure resistance

KV

42

7

Each electric conduction return route resistance

μΩ

≤ 60

8

Gathers floodgate manual operation moment of force

Nm

≤ 150

9

Touched the knife just to gather the position to incline

mm

≤ 2

10

The current carrying part insulates the distance to the place

mm

≥ 160

11

The fracture opens the distance

mm

≥ 200

 

  The contour and installs the size

Chart two SC40301 isolation knife external dimensions

1. Touches place 2. Touches knife 3. Supporting insulator 4. Tension bar insulator 5. The association sensitively installs 6. Circuit breaker 7. Isolates tool rest 8. Moves touches closes 9. Handle

Please contact Ms.Amy YIN --- yinamy9@gmail [dot] com and sikeqd@126 [dot] com

outdoor High vacuum circuit breaker

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.