Breaking capacity | D | N | H | L | ||
Rated current of frame size Inm | 100,160,250,400,630 | |||||
Rated current In | 100 | 16,20,25,32,40,50,63,80,100 | ||||
160 | 16,20,25,32,40,50,63,80,100,125,160 | |||||
250 | 32,40,50,63,80,100,125,160,200,250 | |||||
400 | 200,225,250,300,315,400 | |||||
630 | 315,350,400,500,600,630 | |||||
Rated insulation voltage Ui | 660V | |||||
Rated operating voltage Ue | 380V | |||||
Number of poles | 3,4 | |||||
Rated ultimate short-circuit breaking capacity Icu 380V/50HZ O-CO KA | 100 | 18 | 25 | 70 | 150 | |
160 | 25 | 36 | 70 | 150 | ||
250 | 25 | 36 | 70 | 150 | ||
400 | 35 | 45 | 70 | 150 | ||
630 | 35 | 45 | 70 | 150 | ||
Rated service short-circuit breaking capacity Ics 380V/50HZ O-CO-CO KA | 100 | 18 | 25 | 70 | 150 | |
160 | 25 | 36 | 70 | 150 | ||
250 | 25 | 36 | 70 | 150 | ||
400 | 35 | 45 | 70 | 150 | ||
630 | 35 | 45 | 70 | 150 | ||
Rated impulse withstand voltage Uimp | 6000~8000 | |||||
Dielectric property V | 3000 | |||||
Endurance | Total cycles | 8500 | ||||
Electrical endurance | 1500 | |||||
Mechanical endurance | 7000 | |||||
Ionization distance mm | ≤30/0 | |||||
Over current trip unit | Thermal magnetic release | 100,160,250,400,630 | ||||
Intelligent trip unit | 400,630 |
Molded Case Circuit Breaker