CJX2-Z(LP1-D) series DC coil power contactor
1. Application
LP1-D Series DC Operated AC Contactor is suitable for using in the circuit rated voltage up to 660V AC 50/60HZ, and in rated current 9-95A in AC-3/380V load circuits. For remote controlling circuit making, breaking and frequently starting AC motors. It can be also conbined with the auxiliary contact group, air delay, thermal relay devices etc. It has specialties of equable&reliable action,quick while working.
2.Specification
Type | CJX2-09Z | CJX2-12Z | CJX2-18Z | CJX2-25Z | CJX2-32Z | CJX2-40Z | CJX2-50Z | CJX2-65Z | CJX2-80Z | CJX2-95Z | |
Rated workingcurrent (A) | AC3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
AC4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |
Standardpower ratingsof 3-phasemotors50/60Hz incategory AC-3 | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 |
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |
415V | 4 | 5.5 | 9 | 11 | 15 | 22 | 25 | 37 | 45 | 45 | |
500V | 5.5 | 7.5 | 10 | 15 | 18.5 | 22 | 30 | 37 | 55 | 55 | |
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 33 | 37 | 45 | 55 | |
Rated heat current (A) | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | |
Electrical life | AC3 (x104) | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 |
AC4 (x104) | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | |
Mechanical life (x104) | 1000 | 1000 | 1000 | 1000 | 800 | 800 | 800 | 800 | 600 | 600 | |
Number of the contacts | 3P+NO | 3P+NC+NO |
CJX2-Z(LP1-D) series DC coil power contactor