LC1-D series AC contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz,rated current 95A,for making,breaking,and frequent starting,controlling the AC motor.Combined with the auxiliary contact group,air delayer,machine interlocking device etc,it is combined into the delay contactor, mechanical interlocking contactor,star delta starter, with the thermal relay. it is combined into the electromagnetic starter.The contactor is produced according to IEC60947-4-1.
Type | Rated insulation voltage(V) | Conventional thermal current lth(A) | Rated operation current 380V AC3(A) | Controled power (kw) | Contacts | |||||
220V | 380V | 415V | 440V | 660V | 1000W | |||||
CJX2-0910/0901 | 660V | 25 | 9 | 2.2 | 4 | 4 | 4 | 5.5 | - | 3P+NO/3P+NC |
CJX2-1210/1201 | 25 | 12 | 3 | 5.5 | 5.5 | 5.5 | 7.5 | - | 3P+NO/3P+NC | |
CJX2-1610/1601 | 32 | 16 | 4 | 7.5 | 9 | 9 | 10 | - | 3P+NO/3P+NC | |
CJX2-2510/2501 | 40 | 25 | 5.5 | 11 | 11 | 11 | 15 | - | 3P+NO/3P+NC | |
CJX2-3210/3201 | 50 | 32 | 7.5 | 15 | 15 | 15 | 18.5 | - | 3P+NO/3P+NC | |
CJX2-4011 | 60 | 40 | 11 | 18.5 | 22 | 22 | 30 | - | 3P+NO+NC | |
CJX2-5011 | 80 | 50 | 15 | 22 | 25 | 30 | 33 | - | ||
CJX2-6311 | 80 | 63 | 18.5 | 30 | 37 | 37 | 37 | - | ||
CJX2-8011 | 125 | 80 | 22 | 37 | 45 | 45 | 45 | - | ||
CJX2-9511 | 125 | 95 | 25 | 45 | 45 | 45 | 45 | - |
Type | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-65 | CJX2-80 | CJX2-95 | ||
Closing voltage 50/60Hz(V) | (0.85~1.1) Us | |||||||||||
Releasing voltage 50/60Hz(V) | (0.2~0.75)Us | |||||||||||
Coil power | 50Hz | Closing (VA) | 70 | 70 | 70 | 110 | 110 | 200 | 200 | 200 | 200 | 200 |
Closed (VA) | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||
60Hz | Closing (VA) | 80 | 80 | 80 | 115 | 115 | 200 | 200 | 200 | 200 | 200 | |
Closed (VA) | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 |