Product Detail
Large Caliber Clamp Leakage Current Meter 1.Range:0.0A-3200A; 2.Resolution: 0.1mA; 3.Clamp:108*148mm,RS232 Software

ETCR7100 Super-large caliber Clamp Leakage Current Meter 

Model:ETCR 7100Name:Superlarge Caliber Leakage Clamp MeterFeatures:Super-large caliber, can clamp 160mm flat cable and steel earth wires, high precision, high anti-interference ability. AC current measurement, Current range: 0.0A-3200A, Resolution: 0.1mA, Clamp size 108*148mm

.Technical Specifications

FunctionMeasure AC leakage current, big current (particularly suitable for leakage current measurement of cable and transformer earth steel)
Power6V DC(LR6×4alkaline dry batteries, continuously working for 12 hours)
Test ModeClamp CT, integral mode
Clamp Size108mm×148mm(can clamp electric cable of 108mm diameter, or 160mm×4mmflat cable and steel earth wires)
Measurement RangeAC 0.0mA-3200A
ResolutionAC 0.1mA
Measurement Accuracy(23°C±3°C, below 70%RH,  measured wire at the center of the clamp)AC 0.0Ma~499A    ±2%±5dgt  
AC 500A~999A     ±3%±5dgt  
AC 1000A~2999A   ±4%±5dgt
AC 3000A~4000A   ±5%±5dgt
Measured Wire PositionMeasured wire at approximately the geometric center of the clamp
Data Storage99 sets,  “ FULL ” symbol indicate the memory is full
RS232 InterfaceWith RS232 interface, download data to computer for analysis and management
Communication WireRS232 communication wire, 1.8m
Frequency50Hz ,60Hz automatic identification
Gear ShiftAutomatic shift
Sample RateAbout 2times/second
Line VoltageBelow AC 600Vline measurement
Display Mode4 digital LCD display, length 47mm×width 28.5mm
Meter SizeLength 350mm× Width 180mm× Height 55mm
BacklightSuitable for dim places
Data Hold"HOLD ”symbol appears
Overflow"OL ”symbol appears
Automatic ShutdownAutomaticallyshutdown about 5 minutes after power onto reduce battery consumption
Voltage DetectionLow battery symbol “   appears to remind the replacement of battery when the battery voltage drops below 5.2V.
Weight of Meter1.5kg(with batteries)
Weight of Package3kg(with accessories)
Working Temperature and Humidity-10°C-40°C; 80%rh
Storage Temperature and Humidity-10°C-60°C; below 70%rh
Insulation strengthAC 2Kv/rms(between core and shell)
S afety S pecificationsIEC1010-1, IEC1010-2-032, 2 class of pollution, CAT Ⅲ(600V)
AccessoriesMeter: 1 PC; RS232 Data Line: 1 PC; Disk: 1 PC; Battery (LR6): 4PCS; Meter Box: 1 PC