Thermocouple extension wire
1.Conductors:Positive-Chromel,
Negative-Alumel
2.Insulation:Extruded PVC
3.Overall jacket:PVC
1, SUBJECTThis specification covers the requirements for PVC insulated thermocouple extension cable, type KX,stranded wire, 2x24 AWG, standard tolerances and color coding according to JIS2, TECHNICAL FEATURESA. Conductors:Stranded thermocouple extension wire
Conductor Size (AWG) | No. of Strands & Gauge |
24 | 7/32 AWG (Ø0,20mm) |
B.Insulation:Extruded PVC(105ºC)Nominal Insulation Thickness: 0.30mmColor code - JIS
C. Assembly:Two conductors (positive and negative) parallel construction.D.Overall Jacket:Extruded PVC (105ºC)Nominal Insulation Thickness: 0.30mm
Color code: | Blue or White/blue trace |
(JIS)3, DIMENSIONS AND TOLERANCES
Dimensions / tolerances (mm) |
3.0±0.35 X 4.0±0.35 |
4, CALIBRATION TOLERANCE
Temperature range | Standard tolerance* | Special tolerance* |
0°C to 200°C | ±2,2°C or 0.75% | ±1,1°Cor 0,4% |
Thermocouple type available: KX, JX, TX, EX, NX, RX,SX and other compensating cable like KCA, KCB and so onColor Code available:
Type KX- 2x24AWG PVC/PVC - JIS Thermocouple Extension wire