Welcome to ECVERY
IO module Application in Distributed Control System
IO module Application in Distributed Control System
Supplier Info
[China Supplier]
Contact Person : Mr. Gao John
Tel : 86-21-69956081
Fax : 86-21-69956079
Product Detail
1.Modbus connectivity 2.RS485 network 3.Isolated modules avalible for special applications 4.can be controlled by HMI

HMIO1616 Manual

The main parameters:

Application:

PLC IO expansion

Distributed Control System

Intelligent Building Control

Power Automation System

3..Dimension

4.Installation

IO module for receiving external fault input signals and output control, the module provides 16 input 16 output signals IN and OUT. Module DIN rail mounting.

LED Indicators:

POWER: Flashes to indicate the Power is on;

COMM: Flashes to indicate the unit , when Communicating;

ERR: Error indication, when the something wrong, the red LED lighting;

IN01—IN16: Input indicator, "OFF" when the input is off. "ON" when the input is on;

OUT01—OUT16: Output indicator, the output is "ON" ,when the output is on.;

Warning!

Do not input 220VAC or 380VAC into the power connector, or the IO module will be burn.

In order to not Electric shock, please operate after turn off the power.

The outputs may be used to drive lamps or external relays when more drive capability is required. The outputs are isolated from the logic and they share a common negative terminal. The relay capacity is 220V3A.

Wiring:

1)wiring of the power:

Use isolated power supplies to ensure that the IO modules are not earthed.

Connect 24VDC –  to 39, and 24VDC + to point 41.

2)Wiring of input

The following diagram shows how the digital inputs are connected to potential free switches. The common can be connected to positive or negative as indicated.

3)  Wiring of output

The output can be used with 24VDC or 220VAC.

Control the load directly

Control the big load with Indirectly

4)wiring of the RS485 communications

Connect RS485 (+)A to point 42, and RS485 (-)B to point 43.

Note: Use RS485 shielded twisted cable to prevent electrical noise pickup, The RS485 line should have external over voltage protection to protect from high voltage electrical noise being induced into the RS485 cable. RS485 line is shorter then100 meters, if it is beyond 100 meters, please connect a 120 ohm resistor on the remote end.

5. The terminal

6. MODBUS-RTU Communications 

6.1 Communications interface 

RS485 Communications parameter:

BAUD RATE 9600, 19200 (normal 9600)

DATA BITS 8

PARITY None, Even, Odd (normal None)

STOP BITS 1, 2 (normal 2)

6.2 Communications distance

RS485≤ 1200m

6.3 Communications form

6.3.1 Read Input Status

04 code, specifies

Address+04+ 00+ 01+00+01+crc (word)

Response:

Address+04+02+00(Ho) +00 (Lo) +crc (word)

Data bits format:

Ho means high 8–bit , it is Input1 to Input8

For example: If input1 is On, 0000 0001 0000 0000

Lo means low 8–bit, it is Input9 to Input16

For example: If input9 is On, 0000 0000  0000 0001

6.3.2 Setting the Output Status

0F code specifies:

Address+0F+ 00+01 + 00+10+02+HStatus +Lstatus +crc (word)

Address is the device address,

0F+ 00+01 +00+10+02 is 0F code Fixed format,

HStatus + Lstatus: the output status,

With two bytes, high first, low in the post,

For example:

Set the Output1 on:

Binary: 00000000 00000001,converting to hexadecimal:00 01, It means the Output1 is On.

crc(word)  is check code

Response:

Address+ 0F+ 00+01+00+10+ crc(word)

7 MODBUS terminal address

 

IO module Application in Distributed Control System

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.