Natural gas Generator set Model : 120GF-PT

1.Technical specification

a.Technical specification of gas generator set

Model

120GF-PT

Engine Model

T4190

Alternator Model

SB-CW-120-6.1

Control Panel

PLR-120

Rated Power kW

120

Rated Current A

217

Rated Voltage V

400

Rate Power Factor COSΦ

0.8  Lagging

Rated Frequency Hz

50

Starting Method

24V DC

Voltage Regulation

Automatic

Speed Regulation

Electronic speed regulation

Excitement Method

Brushless

Phase and connection

3 Phase 4 wire connection

Connecting method

Flexible coupling

Cooling method

Water cooling , Fan

Overall dimensions

(L×B×H) mm×mm×mm

3940×1600×1855

Net Weight kg

5300

 b.Technical specification of gas engine

Engine model

T4190

Type

4 –stroke, Spark plug ignition, water-cooled

Cylinder  number

4

Cylinder bore                    mm

190

Stroke Piston                     mm

210

Total displacement          L

23.82

Rated power                 kW

140

Rated speed               r/min

1000

Lub Oil Consumption     g/kWh

≤1.5

Lubricating method

Pressure and splash lubrication

Cylinder number

Output end

1- 2- 3- 4

Ignition mode

SI

Ignition sequence

1-2-4-3

Starting method

24V DC motor starting

Rotation direction

Counter-clockwise (facing output end)

Power output method

Flywheel output

Dimensions L×H×W  mm×mm×mm

2240×1120×1656

Weight                 kg

2800

c.Technical specification of control pane 

Model

PLR-120

Functions

The PLR-120 control panel has comprehensive protecting function

for over-current, short circuit, reverse power, low frequency and low voltage etc.

It also has the functions of automatic quasi-synchronism, load distribution

and automatic power factor adjustment.

PLR-120 can analyze the condition of the grid, once the grid is shut down,

it can cut the gas generator set from the grid until the grid start to work again,

then automatically recover the connection.

The control panel can also cooperate with monitoring instrument, to monitor

 water temp, oil temp, oil pressure and speed of the engine. Once threat

emerges, control panel will alarm and automatically switch off for protection.

Application method

Work with grid connection or single unit operation or parallel operation

2.operating requirement:

a.ambient conditions:

a)Ambient temperature : -40°c~40°c

b)Relative humidity≤95%(35°c)

c)ASL Above Sea Level≤2000m

d)Working atmosphere:  flashing board

b.Requirements for natural gas source:

Natural gas source pressure is in the range of 50-300Kpa.Methane number will be no less than 70% (volume percent), Low heat value for natural gas will be no less than 32MJ/m3. H2S≤50mg/Nm3,Total sulphur content is not more than 480 mg/m3 ,Natural gas should be treated to get rid of free water, crude oil and light oil.