Ads by Google
Name: EVI Low temperature air to water heat pump
Model | heat pump | CAR-12EVI | CAR-12EVI | |
Standard condition | Heating capacity | kw | 10.40 | 11.40 |
kcal/h | 8942.00 | 9802.00 | ||
Hot water supply | T/h | 0.22 | 0.25 | |
Input power | kw | 2.56 | 2.77 | |
Low temperature conditions | Heating capacity | kw | 8.65 | 9.59 |
kcal/h | 7438.00 | 8246.00 | ||
Hot water supply | T/h | 0.17 | 0.18 | |
Input power | kw | 2.60 | 2.80 | |
Ultra-low temperature conditions | Heating capacity | kw | 5.33 | 5.95 |
kcal/h | 4583.00 | 5116.00 | ||
Hot water supply | T/h | 0.10 | 0.11 | |
Input power | kw | 2.50 | 2.70 | |
Standard condition heating input current | A | 12.20 | 4.85 | |
Max running current | A | 17.10 | 7.50 | |
Power | V/Ph/Hz | 220V~50Hz | 380V/3N/50Hz | |
Unit Noise comprehensive index | Db(A) | 55.00 | ||
Dimension | W | mm | 670/883(side) | |
D | mm | 640/363(side) | ||
H | mm | 820/1000(side) | ||
Unit weight | kg | 115.00 | ||
Water temperature control precision | °C | ±2°C | ||
Ambient temperature range | °C | –25°C–43°C | ||
Throttle type | thermostatic expansion valve | |||
Refrigerant | Type | R407C | ||
Refrigerant charge | kg | 2.60 | ||
Max working pressure | bar | 28.00 | ||
Compressor | Type | Efficient fully enclosed type vortex | ||
Qty | pc | 1.00 | ||
Stall Current | A | 90.00 | 36.00 | |
Air-source side heat exchanger | Type | Finned heat exchanger | ||
Qty | pc | 1.00 | ||
Motor power | kw | 0.20 | ||
Hhot water side heat exchanger | Type | Finned heat exchanger | ||
Water flow | m3/h | 1.79 | 1.98 | |
Water pressure down | kPa | 27.00 | ||
Connecting pipe size | DN | 20.00 | ||
Water side max working pressure | kPa | 1000.00 | ||
Suggestion water tank volume | m3 | 1.2–3 |
1,standard condition heating condiiton: air source side heat exchanger inlet air 20/15°C,hot water source intial temp 15°C,end heating temp 55°C.2,Low temp heating condition: air source side heat exchanger inlet air 7/6°C,hot water side intial temp 10°C,end heating temp 55°C.3,Ultra-low temperature heating conditions:air-source side heat exchanger inlet air -15/-17°C,hot water side intial temp 10°C,end heating temp 55°C.
EVI Low Ambient Temperature Air Source Heat Pump