1.Side-mounted 2.Flexible installation 3.With digital temperature controller 4.Can reach high temperature and high accuracy

Side Mounted Cabinet Air Conditioner

Features:

Cooling capacity:200WRefrigerant: R134a Digital control mode, can reach high accuracy. The unit can work perfectly from -40 to +55 Degrees Celsius. Keep the dust, oil fog and moisture from entering the internal of the equipments. IP23 The structure design makes the installation more flexible. And the unit can be installed perfectly in the side or outside wall of the equipment. Totally solve dust and moisture contamination issues caused by ventilation.Applicable for severe ambient environment, such as high temperature, high humidity atmosphere Using natural cooling technologies, energy efficient operation, more reliable than air-conditioning, lower cost. Widely used in telecommunications, broadcasting, electricity, automation and other industries out-door cabinet, IDC room cooling needs. The unit applications: electric equipment control box, battery compartment, and telecommunication equipment and other pertinent equipments, enclosed area climate control such as wireless communication cabinet, battery cabinet, industry control cabinet etc.

Scope:  electric equipment control box, battery compartment, and telecommunication equipment and other pertinent equipments, enclosed area climate control such as wireless communication cabinet, battery cabinet, industry control cabinet etc.

Installation instruction: 

Don't use the equipment in the environments with more dust, oil moisture, corrosive or harsh air. Among them shall not exceed 55°C ambient temperature, and not lower than  0°C, humidity should not exceed 95%.Use M6*10 screws fix flange on cabinet.Drain cannot stress, after the installation must ensure smooth condensate drain, handling or moving the equipment, do not upside down, tilt and collision.                                                                          

Patameter Table:

 

 

Mass Production:

 

 

 

 Application:

 

 

 

 

 

 

 

 

Related Products:

 

 

 

 

 

How to Determine Correct Model of Cabinet cooler

 

Key Point---Calculating Heat Load for your EnclosureTo determine the correct model for your application, it is first necessary to determine the total heat load to which the control panel is subjected. This total heat load is the combination of two factors — heat dissipated within the enclosure and heat transfer from outside into the enclosure.Steps of Calculating Btu/hr.:1. First, determine the approximate watts of heat generated within the enclosure.  Watts x 3.41 = Btu/hr. 2. Then, calculate outside heat transfer as follows:    a. Determine the area in square feet exposed to the air, ignoring the top of the cabinet.    b. Determine the temperature differential between maximum surrounding temperature and desired internal temperature. Then, using the Temperature Conversion Table (below), determine the Btu/hr./ft.2 for that differential. Multiplying the cabinet surface area times Btu/hr./ft.2 provides external heat transfer in Btu/hr.3. Add internal and external heat loads to get total heat load.

 

Temperature Conversion Table

Temperature Differential ° F

Btu/hr/ft.2

5

1.5

10

3.3

15

5.1

20

7.1

25

9.1

30

11.3

35

13.8

40

16.2

Example:    Internal heat dissipation: 650 Watts or 2216 Btu/hr.    Cabinet area: 40 ft.2    Maximum outside temperature: 110°F    Desired internal temperature: 95°FThe conversion table (above) shows that a 15°F temperature differential inputs 5.1 Btu/hr./ft.240 sq. ft. x 5.1 Btu/hr./ft.2 = 204 Btu/hr. external heat load.Therefore, 204 Btu/hr. external heat load plus 2216 Btu/hr. internal heat load = 2420 Btu/hr. total heat load or Btu/hr. refrigeration required to maintain desired temperature.In this example, the correct choice is a 2500 Btu/hr. Cabinet Cooler System.

 

 

 

More details, pls do not hesitate to contact us!

50/60Hz 200W factory price indoor/outdoor environmental protection side mounting industrial panel air condition for telecom use

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.