We have 3 series chillers. LSQ series scroll chiller, LSB sermi hermetic chiller and LSLG series screw compressor chille

there are 3series, so it's can safisfied difference custer mind

LSQ Air Cooled Box Type Chillers

  data                            Model

LSQ-

03AS

05AS

08AS

10AS

12AS

15AS

20AD

25AD

30AD

40AD

Capacity

kW

8.3

13.7

22.1

29.5

34.0

44.1

59.0

68.0

88.2

120

103kcal/hr

7.1

11.8

19.0

25.4

29.2

37.9

50.7

58.5

75.9

103.2

Total Input(kW)

3.1

5.0

7.4

9.7

11.9

15.3

19.4

23.7

30.6

40.5

Total current(A)

5.7

9.7

14.3

18.2

22.1

28.8

36.3

44.1

57.6

64.2

Compressor

Qty

1

1

1

1

1

1

2

2

2

2

Input(kW)

2.55

3.96

6.11

8.06

9.9

12.39

16.1

19.8

24.8

34.10

Current(A)

4.39

7.69

11.41

14.86

18.25

22.70

29.7

36.5

45.4

49.60

Water Pump

Type

CENTRIFUGAL       Water Pump

Input(kW)

0.37

0.55

0.75

0.75

0.75

1.50

1.50

1.50

2.20

2.20

Current(A)

0.75

1.1

1.5

1.5

1.5

3.2

3.2

3.2

4.6

4.6

Pressure head(mHO2)

15

20

22

20

17

25

24

18

22

22

Note:

 

 

 

 

 

 

 

 

 

 

 

1.Test Condition: Chilled water Tin/Tout: 12°C/7°C.Environment Temperature35°C;

 

 

 

 

2. Security operation range: chilled water in: 9~25°C;

 

 

 

 

 

 

 

3.Power supply: 3P-380V-50Hz; Voltage Allowance:±10%, Phase Voltage Allowance:±2%.

 

 

 

4.The data above is got by R22. Data for R134a,R407C etc are available on request.

 

 

 

 

5.There may be change of the dimensions without pre notice. For accurate you are welcome to ask us for installing drawing.

Chillers

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.