UPS Power systems for computer Outstanding Features :
1. Wide Input Range (110-300VAC) to avoids unnecessary discharging of battery life
2. High input power factor (0.98) to matches the latest electricity rule and reduces current consumption
3. A Real Green-environmental Protection Power.
4. Direct Current Cold Start Function
5. Microprocessor controlled operation (DSP) to reduces the no. of hardware components and makes the system simple and reliable
6. IGBT inverter to reduces the heat considerably. Current carrying capacity is high & can handle high in-rush loads
7. High capacity charger (10A) to ensure longer battery backup time
8. Self diagnostic function to makes the system user friendly
9. Overloaded Protection Function
10. Over-temperature Protection
11. Intelligent Fan Speed Control Function to monitor and control almost all functions of your UPS using the software
12. 0.8 load power factor to enhance the ability of different load (comparatively 4 years earlier than same filed)
Applications:
Work stations & Networks
Automatic Control Systems
Automatic and Medical equipment
Laboratory and Medical equipment
Security and Emergency Systems
Banking and Data Processing
Computer and Communications
Model Item | 3C10KS | 3C15KS | 3C20KS | ||
Rated power | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | ||
AC INPUT | |||||
AC Input | Input system | Three phase & earth ground | |||
Range voltage | 380±20%VAC | ||||
Frequency | 50/60Hz | ||||
Voltage range | 115~300VAC±5 @ half load; 176-296VAC±5 @ full load | ||||
Frequency range | 45~55Hz±0.5Hz or 55~65Hz±0.5Hz auto sensing | ||||
Power factor | 0.98 | ||||
Voltage range of bypass | 65VAC×(1±5%)~140VAC×(1±5%) | ||||
BATTERY INPUT | |||||
Battery Input | Type | Lead-Acid maintenance-free | |||
Voltage range of battery | 192/240VDC optional | ||||
Bat Number | 16/20PCS | ||||
Inside batteries | ········ | ||||
Backup Time | Standard ups 1: Half loaded ≥10minutes,Full loaded ≥5 minutes Long backup ups 2: depend on the external batteries | ||||
Charging current | 6A/8A optional | ||||
Battery charged time | Standard ups: 5 hrs to 90% battery capacity | ||||
Long backups ups; Depend on the capacity of external batteries | |||||
AC OUTPUT | |||||
AC Output | Output system | Three phrase & earth ground | |||
Output voltage | 380±20%(inverter output) | ||||
Output frequency | 50±5Hz(line normal, according to line) 50Hz±1%(line abnormal) | ||||
Dynamic voltage transient range | <5% | ||||
Dynamic transient restore | < 60ms | ||||
Waveform | true sinewave | ||||
Power factor | 0.8 | ||||
Overload capability | 105~125%≥ 60s,126~150%≥30s The recovery point is 90% | ||||
Current peak coefficient | 3:1 | ||||
Transfer time | 0ms (AC to DC ) | ||||
< 4ms(AC to bypass) | |||||
Isolation | output tranformer isolation optional | ||||
Efficiency | 90% | ||||
THD | >2% | ||||
INTERFACE | |||||
Interface | LEDand LCD Panel | I/P Voltage, I/P& Frequency,Battery voltage,UPS status, load, temperature,O/P Voltage,Frequency, B/P Voltage,Frequency | |||
Communications | RS232,Intelligient Slot (Web power card, or As400 Card Optional). | ||||
TERMINALS | |||||
Power Outlets | terminals | ||||
FUNCTION | |||||
Function | Cold start | DC Power On | |||
Automatic Charge | Automatically Charge when UPS is off | ||||
Automatic Restart | Automatic Restart if main power coming after battery mode shutdown | ||||
Frequency | 50HZ/60HZ Auto Adjustable | ||||
Alarm | AC/DC input under abnormal ,overload condition and inverter problems | ||||
Protection | AC input or output above or below the range of voltage Overload ,over temperature and short circuit protection | ||||
ENVIRONMENT | |||||
Environment | Temperature | -5~45 Degree | |||
Humidity | 20% to 90% | ||||
Noise level | ≤55dB | ||||
PHYSICAL CHARACTERISTICS | |||||
Physical | Net Weight (KGs) | 25 | 32 | 32 | |
Gross Weight (KGs). | 34 | 41 | 41 | ||
Product Dimensions (L*W*H* mm) | 500*250*615 | 500*250*615 | 500*250*615 | ||
Packing Dimensions (L*W*H* mm) | 675*375*850 | 675*375*850 | 675*375*850 |