T- II 600 A Deadbreak Connector with 200 A interface and optional capacitive test point.
Tests are conducted in accordance with IEEE Standard 386.
AC 60 Hz 1 Minute Withstand
34 kV
Minimum Corona Voltage Level
11 kV
Tests are conducted in accordance with Tenseng Power Systems requirements.
Physical Inspection
Periodic Dissection
Periodic Fluoroscopic Analysis
One-body shielded and one-time injection molding technique which ensured high Screened and Insulation
The KYLIN BT-15/600 Deadbreak Tee connector is a fully shielded and insulated connector, connected with underground ranging from 35 to 500 mm2(conductor cross section). It meets the requirements of ANSI/IEEE Standard 386-"Separable Insulated Connector Systems".
Using EPDM as raw material, KYLIN manufactures Deadbreak Tee Connector with one-body shielded and one-time injection molding technique. Deadbreak Tee Connector is used to connect underground cable to padmounted transformers, submersible transformer, switchgear and 600A Junctions equipped with deadbreak bushings.
The test point is available for installing Voltage Indicator.
600A Cable Accessory Ratings:
Rated Voltage 15kV/25kVRated Current 600ARated Short Time Withstand Current 20kV/3s
Dynamic Stability Current 50kAPower Frequency Withstand Voltage 40kV, 5minImpulse Withstand Voltage 95KVPartial Discharge ≤3PcCable Conductor Cross Section Range 35mm2__500mm2
Class T-II Deadbreak Connector 600A 15kv