KTO 011 Thermostat
KTO 011: Thermostat (normally closed); contact breaker for regulating heaters.
KTS 011: Thermostat (normally open); contact maker for regulating of filter fans and heat exchangers or for switching signal devised when temperature limit has been exceeded.
Certificate: CETechnical Data
Switch temperature difference | 7K(±4K tolerance) |
Sensor element | Thermostatic bimetal |
Contact resistance | 10m O |
Service life | 100,000 cycles |
Max. Switching capacity | 250VAC, 10(2)A 120VAC, 15(2)A DC 30W |
EMC | Acc. To EN55014-1-2, EN61000-3-2,EN61000-3-3 |
Connection | 2-pole terminal, clamping torque 0.5Nm max.: Rigid wire 2.5 mm2 Stranded wire (with wire end ferrule) 1.5 mm2 |
Mounting | Clip for 35mm DIN rail,En50022 (or for exit filter EF 118 series) |
Casing | plastic according to UL94-HB , black |
Dimensions | 60x33x43mm |
Weight | Approx.40g |
Fitting position | Variable |
Operating/Storage temperature | -45 to + 80 (-49 to +176 F) |
Protection type | IP20 |
Setting range | Art. No. Contact Breaker (NC) | Art.No. contact Maker(NO) |
0 to +60 | 01140.0-00 | 01141.0-00 |
-10 to +50 | 01142.0-00 | 01143.0-00 |
+20 to +60 | 01159.0-00 | 01158.0-00 |
+30 to +140°F | 01140.9-00 | 01141.9-00 |
+14 to +122°F | 01142.9-00 | 01143.9-00 |
0 to +60 | 01146.9-00 | 01147.9-00 |
KTO 011small,compact,Mechanical thermostats