The Vehicle Grounding System is designed for top and bottom loading of tank trucks, rail cars, etc..In the event of an overfill condition, the overfill sensors will send a signal through the output relay to the terminal automated loading system to shutdown the loading operation.The systems provide overfill protection as well as grounding verification.
Model: SLA-S-IIC For Top Loading
Specifications:
Input Power: 85VAC to 250VAC @ 47 to 440Hz
Input Current: <35mA
Respond Time: < 2 Seconds
Output Signal: 30VDC @ 10A / 250VAC @ 8A
Ingress Protection: IP65
Clamp and Spiral Cable: Extendable to 6m(20ft.)
Operation Temperature:-40°C to +60 °C
Alarm Volume: >90dB
Certification: ExdiaIIBT4
Features & Benefits:
Audible and visible alarms.
Upon the loss of a ground connection or an overfill condition, the system will send a signal to immediately shut off the loading operation.
An LED display provides the resistance value of the ground connection.
The overfill sensor has a continuous sefl-check and alert feature to insure the system is working properly.
Vehicle Grounding System(overfill detection system for oil truck)