Aluminum Core PVC Insulated Steel Tape Armored PVC Sheathed Power Cable
Aluminum Core PVC Insulated Steel Tape Armored PVC Sheathed Power Cable
Supplier Info
[China Supplier]
Contact Person : Ms. peng alian
Tel : 86-25-57102489
Fax : 86-25-57119489
Product Detail
Aluminum Core Power Cable 1.manufacturer with decades 2.ROHS,CCC,ISO,UL,CE 3.superior service timely

Product Description

The PVC insulated power cable and fire resistant cable are suitable for fixed laying in power transmission and distribution lines with A. C. 50Hz and voltage rating of up to or including 6KV. Product Description: 1. Conductors: Copper or aluminum. 2. Both armored and non-armored type power cables are available. 3. Voltage rating: 0.6/1kV 3.6/6kV. 4. PVC or PE sheathed. 5. Number of cable cores: One core (Single core), two cores(Double cores), three cores, Four cores (Four Equal-section-area cores or three equal-section-area cores and one smaller section area neutral core), Five cores (Five equal-area cores or three equal-section-area cores and two smaller section area neutral cores). 6. Standards: Chinese national standard GB 12706 and GB 12666.6(equivalent to IEC 60502 and IEC 60331) IEC, BS, DIN, ASTM, CSA, NFC, AS, GOST etc. Or other special characteristics as customers request. Description

 Type

Description

No. of cores

Nominal cross section of conductor

VLV

Aluminium conductor/PVC insulation/PVC outer sheath Power Cable

1, 2, 3, 4, 3+1,5, 4+1, 3+2

1.5~800mm2

VLY

Aluminium conductor/PVC insulation/PE outer sheath Power Cable

1, 2, 3, 4, 3+1,5, 4+1, 3+2

1.5~800mm2

ZA-VLV ZB-VLV ZC-VLV

Aluminium conductor/PVC insulation flame-retardant Power Cable

1, 2, 3, 4, 3+1,5, 4+1, 3+2

1.5~630mm2

Operating Characteristics

Rated voltage: 0.6/1(1.2)kV

Max. permissible continuous operating temperature of conductor: 70 °C

Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:

Nominal cross section of conductor ≤300mm2: 160 °C

Nominal cross section of conductor >300mm2: 140 °C

The ambient temperature under installation should not be lower than: 0 °C

The bending radius of cable is recommended as following:

For single core cable: not less than 20 times of the diameter of cable

For multi-core cable: not less than 15 times of the diameter of cable

Application

The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.

Manufacturing Standards

GB/T 12706-2008, IEC 60502-1

Aluminum Core PVC Insulated Steel Tape Armored PVC Sheathed Power Cable