Product Detail
AAC Conductor 1.Material:Aluminium; 2.Standard:BS215,BS EN50182, DIN 48201,ASTM B231.

AAC (All Aluminium Conductors)ASC (Aluminium Stranded Conductors)

1 DescriptionBare concentric-lay-stranded aluminium wires constructed with a straight round central aluminum wire surrounded by one or more layers of helically laid aluminium wires. The most commonly used stranding consists of 7, 19, 37, 61 and 91 wires.In all constructions, the successive layers shall have opposite directions of lay, the outermost layer being right-handed.

2 ApplicationUsed in overhead electric power transmission and distribution lines with various grade voltages.The most favoured overhead bare homogeneous conductors for primary and secondary distribution lines with relatively short spans where high mechanical strength is not required.

3 Manufacturing StandardsGB/T 1179-2008, IEC 61089, EN 50182, DIN 48201 Part 5, BS 215 Part 1, ASTM B231 or as required.

Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Code numberAreaNumber of wiresWire     diameterConductor diameterLinear massRated strengthD.C. resistance at 20oC
mm2No.mmmmkg/kmkNΩ/km
1615.971.75.143.43.021.7986
2524.272.16.366.34.361.1787
3534.472.57.593.96.010.8317
5049.5739135.28.410.5776
5048.3191.89132.98.940.5944
7065.8192.110.5180.911.850.4367
9593.3192.512.5256.316.320.3081
120117192.814321.519.890.2456
150147.1372.2515.8405.726.480.196
185181.6372.517.5500.931.780.1588
240242.5612.2520.3671.143.660.1193
300299.4612.522.5828.552.40.0966
Technical Characteristics Based on Standard BS 215-1
Code nameNominal aluminium areaStranding and wire     diameterSectional areaApprox. overall diameterApprox. massCalculated D.C. resistance at 20oCCalculated breaking load
mm2No./mmmm2mmkg/kmΩ/kmkN
MIDGE227/2.0623.336.18641.2273.99
ANT507/3.1052.839.31450.54198.28
FLY607/3.4063.5510.21740.45059.9
WASP1007/4.3910613.172900.270216
HORNET15019/3.25157.616.254340.182525.7
CHAFER20019/3.78213.218.95870.134932.4
COCKROACH25019/4.22265.721.17310.108340.4
BUTTERFLY30019/4.65322.723.258880.0891648.75
Technical Characteristics Based on Standard ASTM B231
Code WordsSizeAreaNumber of wiresWire     diameterConductor diameterLinear massRated strengthCalculated D.C. resistance at 20oC
AWG or kcmilmm2No.mmmmkg/kmkNΩ/km
Oxlip4/0107.274.4213.26295.2170.268
Tulip336.4170.5193.3816.9469.527.30.1688
Cosmos477241.7194.0220.1664.8370.1194
Orchid636322.3373.3323.31886.950.40.0895
Arbutus795102.8373.7226.04110961.80.0717