Ads by Google
12/20(24)kv Single core aluminum conductors XLPE insulated aluminum wire armored to IEC 60502-2 cables. Cable Construction: 1. Aluminum conductor 2. Semiconductive conductor screen 3. XLPE insulation 4. Semiconductive Insualtion screen. 5. Copper tape screen 6. Bedding 7. Aluminum amour 8. Outer sheath.
Rated Voltage | KV | 12/20(24)KV | ||||||||||||
Nominal area of conductor | mm 2 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 |
Conductor diameter(MAX) | mm | 8.4 | 9.9 | 11.6 | 13 | 14.5 | 16.1 | 18.4 | 20.6 | 23.7 | 26.6 | 29.8 | 33.6 | 37.6 |
Weight of conductor(Approx) | Kg/Km | 125 | 180 | 250 | 313 | 386 | 486 | 637 | 800 | 1024 | 1318 | 1672 | 2231 | 2745 |
Insulation thickness(Nominal) | mm | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.6 | 2.8 | 3 | 3.2 | 3.2 | 3.2 | 3.2 |
Separation sheath thickness | mm | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.3 | 1.4 | 1.4 | 1.5 |
Armour wire diameter(Nominal) | mm | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 2 | 2 | 2 | 2 | 2.5 | 2.5 | 2.5 | 2.5 |
Outersheath thickness(Nominal) | mm | 1.8 | 1.8 | 1.9 | 1.9 | 2 | 2 | 2.1 | 2.2 | 2.3 | 2.5 | 2.6 | 2.7 | 2.9 |
Approximate overall diameter | mm | 26.0 | 28.0 | 29.5 | 31.0 | 32.5 | 35.0 | 37.5 | 40.5 | 44.0 | 49.0 | 52.5 | 57.0 | 61.0 |
Approximate cable weight | Kg/Km | 810 | 980 | 1170 | 1260 | 1390 | 1660 | 1950 | 2320 | 2710 | 3440 | 4090 | 4890 | 5680 |
Minimum bending radius of cable(during installation) | mm | 387 | 417 | 438 | 461 | 485 | 522 | 563 | 605 | 660 | 732 | 786 | 849 | 915 |
Maximum DC resistance of conductor at 20 degree | ohm/Km | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 | 0.125 | 0.1 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Approximate AC resistance of conductor at 90 degree | ohm/Km | 0.822 | 0.568 | 0.411 | 0.325 | 0.265 | 0.211 | 0.162 | 0.13 | 0.102 | 0.080 | 0.064 | 0.051 | 0.043 |
Approximate reactance at 50Hertz | ohm/Km | 0.13 | 0.12 | 0.12 | 0.11 | 0.11 | 0.11 | 0.10 | 0.10 | 0.10 | 0.10 | 0.10 | 0.09 | 0.09 |
Approximate impedance at 50Hertz | ohm/Km | 0.83 | 0.58 | 0.43 | 0.29 | 0.24 | 0.19 | 0.16 | 0.14 | 0.13 | 0.13 | 0.11 | 0.10 | 0.09 |
Approximate capacitance of cable | uf/Km | 0.34 | 0.38 | 0.43 | 0.47 | 0.51 | 0.56 | 0.61 | 0.63 | 0.65 | 0.69 | 0.73 | 0.79 | 0.85 |
Approx. charging current per phase at Uo=12KV and f=50HZ | mA/m | 0.38 | 0.43 | 0.49 | 0.53 | 0.58 | 0.63 | 0.69 | 0.71 | 0.74 | 0.78 | 0.83 | 0.89 | 0.96 |
Sustained current ratings | ||||||||||||||
1.Laid direct,ground temp.30 degree &g=1.2 degree m/W,depth of laying=0.8m,laid in trefoil touching | A | 151 | 187 | 223 | 249 | 280 | 316 | 360 | 405 | 454 | 507 | 570 | 623 | 676 |
2.Drawn into ducts,ground temp.30 degree &g=1.2 degree m/W,depth of laying=0.8m,laid singly | A | 151 | 187 | 218 | 245 | 267 | 298 | 338 | 374 | 405 | 445 | 490 | 525 | 570 |
3.Laid in air in trefoil touching,Ambient temp.35 degree | A | 179 | 221 | 271 | 327 | 350 | 400 | 469 | 534 | 616 | 708 | 810 | 902 | 994 |
One second short circuit current rating of conductor | kA | 4.70 | 6.58 | 8.93 | 11.28 | 14.10 | 17.39 | 22.56 | 28.20 | 37.60 | 47.00 | 59.22 | 75.20 | 94.00 |
21KV Aluminum Conductor XLPE Insulation PVC Bedding Steel Wire Armored PVC or HDPE Outer Sheath Electric Cables (CU/XLPE/SWA/PVC