DPF68B Direct Current (DC) Power Supply Distribution Cabinet
DPF68B Direct Current (DC) Power Supply Distribution Cabinet
Supplier Info
[China Supplier]
Contact Person : Ms. Feng Emma
Tel : 86-20-85163557
Fax : 86-20-82305652
Product Detail
DC power supply distribution system, configurable input is 0~300A fuses. 1A, 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A.

Product Introduction

1. Overview

Please read this manual in detail first before installing this equipment.

This equipment is mainly applied in computer room for frame power distribution. It is installed at the top of the frame in the computer room, providing direct current power supply and the alarm indication for the distribution frame.

 

Main function: With direct current (DC) power supply distribution system, configurable input is 0~300A fuses. The configurable output branches are 1A, 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A. The concrete capacity configuration is specified by the customer.

 

According to the profession standards, there are two alternating current (AC) electric outlets at the bottom of this equipment, it is provided to the customer’s testing instrument, etc. (when in usage, you have to connect external AC power supply)

Refer to Table 1-1 for the size and configurations.

Table 1-1                   Size and Configurations

Model DPF68B

Size

Width*Depth(mm)

300×150, 600×200, 600×300

Height Series(mm)

2000, 2200, 2600

Input Config.(fuse)

Capacity

2-line fuse

Specification

0~630A

output config.( air switch or fuse)

Standard capacity

30 branches or 48 branches

Max. capacity

30 branches or 48 branches or tailor- made

 Specification (A)

1/2/4/6/10/16/20/25/32/40/50/63

 

Notes: The above configuration and size can be tailor-made according to the customer demands.

 

 

 

2. Main Technical Specifications

Refer to working condition in Table 1-2.

   Table 1-2                     Working Condition

Item

Normal usage condition

Limit usage condition

Environment temperature

10~40°C

5~45°C

Relative humidity (at 25°C)

≤80%

≤85%

Atmospheric pressure

70~106kpa

Alarm electric circuit working voltage

-48V±2.4V

Reliability anticipation

MTBF=1.5×105 hours

      

3. Technical conditions

1) Adopt second-class distribution method;

2) Separate the working ground and the protection ground;

3) The direct current (DC) power supply is from inlet end to output end, allow the general voltage reduction no more than 0.3V at the rated loading;

4) All alarm signals are all not jammed;

5) It requires insulation electric resistance and stress.

Points to ground insulation electric resistance of the direct current (DC) power supply distribution system ≥ 30MΩ (direct current DC 500V measured).