Mine explosion-proof ,high voltage ,vacuum ,distribution equipment, Mechanical life of the breaker is no less than 10 thousand

 

Mine explosion-proof high voltage vacuum distribution equipment

Applications

The high-voltage vacuum distribution equipment issuitable to provide reliable control and protection for insulated neutral or arcsuppression coil grounding power supply and transforming system under the coal well with explosive gases and coal soot, with the rated voltage of 10kV, rated frequency of 50Hz and rated current of 630A. Besides, its also suitable for direct starting the electro-motor. The device has 4 structures of a, b, c, d ,to enable different application modes such as power receiving, power feeding,contact, networking, and direct control and so on.

Features

1. The advanced CPU technology is adopted in the protector, which has enhanced function independence of individual parts and practicability of the system. Besides,the high-resolution A/D converter and the detection method of single measuring range are also used in the device, which has greatly enhanced the accuracy of data collection;

2. It adopts blue-backlight Chinese LCD display, which enables data display and all

operations more intuitive;

3. It has the function of detection and display of the power factor and degree of imbalance between the phases as well as display of electricity consumption (active component) and real-time clock and so on;

4. The high-voltage vacuum circuit breaker with spring mechanism is adopted for

breaking principle components;

5. It can provide protection in such cases as overload, short circuit, electricity

leakage, insulation monitoring, overvoltage, undervoltage, three-phase imbalance

etc.;

6. It has the RS485 communication function, which can network 2~999 protectors

into the LAN or Internet with connectors.

Main technical parameters

 

Rated voltage

3.3KV6KV10KV

Maximum working voltage

3.6KV7.2KV12KV

Rated current

50A100A 200A 315A 400A500A 630A

Rated frequency

5OHZ

Rated short-circuit breaking current

12.5KA

Rated (peak) short-circuit switching current

31.5KA

Rated peak withstanding current

31.5KA

Rated short-time withstanding current

12.5KA

Rated thermal stable time

2s

Rated breaking times of the short-circuit current

30 times

Mechanical life of the breaker

No less than 10 thousand times

Service life of the disconnecting switch

No less than 2,000 times

 