/Basic Parameters
5.1. Type LMGR20-1000-30
5.2. Network Rated Voltage 20 KV
5.3 Re-circuit Voltage 11.5kv
5.4 Rated Frequency 50Hz
5.5 Rated Resistance 12Ω
5.6 Power on hours 30s
5.7 Re-circuit Current: 1000A
5.8 Stalling Type Outdoor
6 /Resistor Parameters
6.1 Resistance Unit Code
6.2 Element Material Cr20Ni25
6.3 Required Current for 30s 1000A(for 30s)
6.4 Resistance Tolerance: +5%
7/Earth Current Transducer
7.1 Type LZZBJ9-24
7.2 OTY 1
7.3 Rated Current Ratio, Secondary Capacity: 1000/5A 15VA
7.4. Accuracy class 10P10
8.
8.1. Safe distance is above 200mm
8.2. The elements of resistor can interchange
8.3. IP of the resistor is IP23
8.4 Material of the Metal Frame: 2MM Carbon Steel, Hot Dip Galvanized Enclosure
9/Others
9.1 Manufactory should offer the Withstand Voltage Test and Temperature Rise Calculation reports
9.2. Manufactory provide the resistance value and insulated resistance value for the
customers.
9.3. We supply the overall dimension and installation drawing.
Neutral grounding resistor