Welcome to ECVERY
RF9800 Single-phase Parameter Measuring Instrument/power meter
RF9800 Single-phase Parameter Measuring Instrument/power meter
Supplier Info
[China Supplier]
Contact Person : Ms. Li Kaixuan
Tel : 86-755-83324500
Fax : 86-755-82736668
Product Detail
RF9800 Single-phase Parameter Measuring Instrument/power meter,Voltage,current,Power Factor,W

 

GENERAL TECHNO-INDEX

Warming up time: Approximately 10 minutes

Environmental temperature and temperature scope0∼40,20%∼80%RHNo dewdrops

Isolation impedanceSignal input terminalsOuter shellPower supply input terminals mutual impedance more than 10MΩ

Withstanding voltageSignal input terminals and outer shellSignal input terminals and power supply input terminals AC2000V with each other within 1 minute & DC2200V with each other within 1 minute

Power supply220 ± 22V,Frequency50Hz / 60Hz

Power dissipationApproximately 5W

WeightApproximately 4.0 kg

Dimensions400mm×340mm×180mm

DISPLAY FUNCTION

Display category7 segments LED,display window amounts and display contents

Models

Windows

Display content

Test range

RK9800

A

V

75V/150V/300V/600V

B

A

0.5A/2A/8A/20A

C

W

1W~1200W

D

PF

-1.000~+1.000

RK9901

A

V

75V/150V/300V/600V

B

[m]A

0.5A/2A/8A/20A

C

PF

PF-1.000~+1.000

Hz

Base frequency :45Hz ∼ 65Hz,bandwidth: 5kHz

W

1W~1200W

BASE ERROR ACCURACY

Voltage

Conditions

±0.4% rdg+0.1% range+1 digit

Current

±0.4% rdg+0.1% range+1 digit

Power

±0.4% rdg+0.1% range+1 digit

Power factor

±(0.004+0.001/ rdg+1 digit)

Frequency

±(0.1% rdg+1digit)