Working principle:
The UPS is a multiple proctection power system with inverting output isolation transformer.When mains is normal,UPS will output directly,the battery is charged at the same time.When mains is off or abnormal,the battery will change into AC to output,ensuring the user can get the high quanlity electricity.
Technical parameter for line-interactive UPS HT2-5KVA:
Model | HT2000 | HT3000 | HT4000 | HT5000 | ||||
Capacity | 2000VA | 3000V | 4000VA | 5000VA | ||||
Work mode | Low frequency line interactive | |||||||
Input | Voltage | 145- 275Vac (single phaseL+N+G) | ||||||
Frequency | 50Hz±10% | |||||||
COSΦ | ≥90% | |||||||
Output | Mains output Voltage | 220Vac ±10% (single phaseL+N) | ||||||
Battery invertering output Voltage | 220Vac ±3% (single phase L+N) | |||||||
Frequency | 50Hz±1% (battery mode) | |||||||
COSΦ | 0.8(lag) | |||||||
Waveform | Sine wave | |||||||
Wave Form distortion | Linear load<3% | |||||||
Non linear load<5% | ||||||||
Overload protection | <150%→20s >150%→10ms | |||||||
Transfer time | 5ms | |||||||
Charge current | 1-10A | |||||||
Display panel | LED: green light for mains output;yellow light for inverter output;red light for faults LCD(optional) input/output battery voltage;input/output frequency;number of load and condition | |||||||
Protection function | overload;short-circuit;low/high voltage battery | |||||||
Battery | Sealed lead acid maintenance-free battery | |||||||
External battery voltage | 48VDC | |||||||
Number of battery | 12V4PCS (standard type with internal battery 12V7AH4PCS) | |||||||
Ambient | Temperature | 0 - 40oC | ||||||
Humidity | 0 -95% | |||||||
Communication | 9Pin D type connector (RS232) | |||||||
Enclosure Size (WxDxH) mm | 440*245*300 | |||||||
Packing Size (WxDxH) mm | 550*305*350 | |||||||
Weight(kg) | 33.5 | 36.5 | 37.5 | 38.5 | ||||
*(L) - long backup Version;(S)- Standard type with internal battery( 12V7AH). | ||||||||
4000VA Cost-effect Line Interactive UPS with 5ms transfer time