WST-C2 type intelligent temperature controller introduction

The function of each button is clearly, through the relay hige to achieve automatic control, temperature controller will according to the changes and automatically shut off or start the control equipment.

1. Technical specifications:

Temperature measurement range:

0-125degree

Sensor:

DS18B20

Resolution:

0.1degree

The control accuracy:

0.1 degree

Output type:

relay (contacts capacity of 250 V, 5A),

Shell size:

87 mm *135 mm *45 mm

Working voltage:

AC85 ~ 242 V  50 Hz / 60 Hz

Types of control:

Heating-typeCold-typeAutomatic heating/cold type

2. The parameters set operation:

Shows an energized observation, not changing the set, the original record the data set with automatic control operationChange is accused of temperature setting: It is energized, long press SET key, access to menu mode, according to the corresponding parameters on the adjustment, press " increase " or " reduce " button to change the SET value, " increase " is used to increase the temperature setting, " reduce " used to reduce the temperature setting, Press the "SET" save Settings of data, then the temperature controller to return to control operation. In more than 15 seconds set state not operation will automatically save Settings data and returns status.Of actual use please do not set the limit higher than the upper.Temperature sensor short-circuit, open circuit fault tip Err.

3. Installation: instrument temperature must be held at around -5degree ~ 65degree, the instrument must be placed in no damp and high pressure situation, and ventilation to easy to heat dissipation. 

4. Wiring: put the device that need to control inserted in a socket, the power supply must match the manual of the instrument.

5. Parameter:

symbols

Description

range

Default value

H1

The first group High limit

0-124.9degree

26degree

L1

The first group Low limit

25degree

H2

The second group High limit

32degree

L2

The second group Low limit

30degree

HH

Need to customize

High alarm limit

1-124.9degree

95degree

LL

Low alarm limit

0-124.9degree

10degree

HC1

Group 1 Cooling/heating switches

00~70

00

HC2

Group 2 Cooling/heating switches

00~70

01

Note: HC heating/cooling state switch data

00 = heating,01= cooling  Other values are not output