Product Detail
material: high quality sillicon rubber voltage class:15kV 25Kv 35kV easy installation price: see by contact (very cheap)

Straight Joints

Type ZJTLS

Up to 36 kV

 

Application

For jointing copper wire screened or copper tape screened three-cores or single-core cable to be laid in air or directly buried.

Table 16

Table X

Cable insulation range

Use for

8.7/15 kV joint

Cable

Insulation

Code

Cable Insulation

Range

Cable Cross Section

Inches

mm

mm2

A

.67~.79

17.0~20.0

25,35,50

B

.79~.98

20.0~25.0

70,95,120

C

.98~1.18

25.0~30.0

150,185,240

D

1.18~1.42

30.0~36.0

300,400

E

1.42~1.50

36.0~38.0

500

Table 17

Table X

Cable insulation range

Use for

12/20 kV joint

Cable

Insulation

Code

Cable Insulation

Range

Cable Cross Section

Inches

mm

mm2

A

.79~.98

20.0~25.0

35,50,70

B

.98~1.18

25.0~30.0

95,120,150

C

1.18~1.42

30.0~36.0

185,240,300

D

1.42~1.50

36.0~38.0

400,500

Table 18

Table X

Cable insulation range

Use for

18/30 kV joint

19/33 kV joint

Cable

Insulation

Code

Cable Insulation

Range

Cable Cross Section

Inches

mm

mm2

A

.95~1.06

24.0~27.0

35

B

1.02~1.34

26.0~34.0

50~70

C

1.18~1.58

30.0~40.0

95~185

D

1.54~1.77

39.0~45.0

240~300

E

1.73~2.01

44.0~51.0

400~500

Example: A joint is required for a 8.7/15kV, 300mm2 compacted, three core copper tape screen cable with a diameter over core insulation of 30.6mm. Order a ZJTLS15-300/3 –DT joint.