Product Detail
-Output Current up to 20KA -Current injection, CB and Impact test - Automatic or Manual mode -Over current & zero protection

Product Features:

-The max. current output up to 20000A,Impact test below 20000A;

-Three function in one body: current injection, CB test and impact test;

-Current injection can be operated by automatic or manual mode;

-Can measure breaker’s action time and action current;Value holding for CB action current

-Current preset and over current protection; Zero Protection; Alarm

-Suitable for current injection, temperature rise test

-Cool by fans;

-On trolley so that can be moved easily.

Specifications:

-Input:380Vac,315.8A,50Hz

-Output Current and its duration:

0~2500A,continuously Up to 4000A, onehour, off 30 minutes

Up to 7000A, 15 minutes, off 15 minutes

Up to 13000A, 1minutes, off 15 minutes

Up to 20000A, 10 seconds, off 15 minutes

-Output opening circult voltage/short circuit voltage:6V

-Capacity:120KVA

-Over current protection:7ms

-Range for CB action time:0.0001~999.9999 seconds,resolution:0.0001 second

-Current output accuracy≥0.5% full scale

-Insulation resistance≥2MΩtested with 500V mega meter.

-AC withstand: 3KV, 1 minute.Input coil upon output coil & earth; output coil upon input coil & earth-Dimensions & Weight:

Primanry current for net size & weight:1110×1130×900mm,265Kg

Control Panel for net size & weight:960×650×200mm,275Kg

Primanry current for Transportation size & weight:1250×1230×1110mm,300Kg

Control Panel for transportation size & weight:1080×770×2190mm,330Kg

Acknowledgement for Order

-This model is made according to customer’s demands.

-Lead time: about 8 weeks

-It’s better for us to obtain your requirements in details as that we can achieve your functions fully. Meanwhile, reduce your cost.-It’s better for you to order output current cables with primary current test set, so that we can balance equipment performanceroundly. Besides, it is convenient for equipment Routine test.

-New Model with PLC control/Touch Screen is ready to order.

Order Information:

-Split structure, two blocks

-Included Accessories:

Input power cables, 60mm2×3 meter, 2 pcs.

Output power cables for control panel/ Input power cables for primary tester, 60mm2×3 meter, 2 pcs

Control cable, 2 pcs. One connects control panel and primary tester. Another for connects control panel and CB.

Ground leads, two pcs. One for primary tester, another for control panel

Zero lead, one piece

Output current cables, copper bolts, nuts, optional for order.

( function(){ var aBigImageSrc = [ 'http://i00.i.aliimg.com/photo/v1/557072914_1/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' , 'http://i00.i.aliimg.com/photo/v1/557072914_2/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' , 'http://i00.i.aliimg.com/photo/v1/557072914_3/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' , 'http://i00.i.aliimg.com/photo/v1/557072914_4/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' , 'http://i00.i.aliimg.com/photo/v1/557072914_5/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' , 'http://i00.i.aliimg.com/photo/v1/557072914_6/Single_Phase_20000A_Primary_Current_Injection_Test.jpg' ]; var oProductShow = new AE.run.minisite.productShow(); oProductShow.init( { 'aImgSrc': aBigImageSrc } ); } )(); Single Phase 20000A Primary Current Injection Test Set