1 Resistance load equipment: 50KW
2 Power factor: 1.0
3 Test voltage: three phase AC voltage 400V
4 Frequency: 50--60Hz
5 Active power step:
1KW X 5 2KW X 3
3KW X 2 5KW X 3
10KW X 2
6 Normal Operational Conditions
In summer the ambient temperature is 45,humidity is 90%.In winter the ambient temperature is -20, humidity is 50%
7 ventilation power and the control power of the load bank are single phase 3 wire ( 220V + N + PE), total control power is 1 KW.
8 Cooling mode: forced air convection, the fanner with axial-flow, the direction of the air is coming from the bottom and outgoing from the above.
9 Controlling mode: Manual control.
10 Load bank rated power error: thermal state: -4, cold state: -2.
11 Protection device: over-current, short-current, over-load protection for the fanner.
12 the temperature for load bank outlet is 250-300
13 IP for main return circuit: IP23
14 Insulation degree for motor: F
Insulation degree for load main return circuit and control return circuit: F
15 Working mode: continuous
16 Weight: 180KG
Resistive Load bank