Welcome to ECVERY
Pad mounted Transformers
Pad mounted Transformers
Supplier Info
[China Supplier]
Contact Person : Ms. Ju Maggie
Tel : 86-570-4016599
Fax : 86-570-4016599
Product Detail
The ZGS11 Series Pad mounted Transformers are widely used in high-rise buildings, hotels, villas safe and reliable.

The ZGS11 Series Pad mounted Transformers are in accordance with the national standard JB/T10217-2000 Padmounted Transformer and enterprise standard Q/321284JCA39-2003 Padmounted Transformer.

The ZGS11 Series Padmounted Transformers are widely used in high-rise buildings, hotels, villas, residence communities, parks, and street lamps.

Structural features

The core uses high-quality cold-rolled grain orientation silicon steel sheet. The no-load loss of the product is 30% lower than the 9 series. The transformer chamber, high-voltage chamber, and low-voltage chamber are in optimized combination. They are pre-formed in the factory. Therefore, the structure of the product is simplified. The size is about 1/3 of that in China with the same capacity. The transformer is suitable for residence communities, commercial entertainment center, and street lamps in cities. It will be useful for saving the land resource. Products are hermetically-sealed and insulated without any exposed electrified component and are safe and reliable. Products can be used on terminals and looped network. The transformation is convenient. Cases are of corrosion protection design. Special spray painting treatment is used. Products are suitable for using under severe environment.

Performance characteristic parameters

Capacity

kVA

Voltage combination

Connection symbol

No-load loss

W

No-load current

%

Load loss

75°C   W

Short-circuit impedance

75°C  %

High voltage

KV

Tapping scope

Low voltage

KV

30

6

6.3

10

20

±2*2.5%

0.4

Dyn11

100

2.1

600

4

50

130

2.0

870

80

180

1.8

1250

100

200

1.6

1500

125

240

1.5

1800

160

280

1.4

2200

200

340

1.3

2600

250

400

1.2

3050

315

480

1.1

3650

400

570

1.0

4300

500

680

1.0

5100

630

810

0.9

6200

4.5

800

980

0.8

7500

1000

1150

0.7

10300

1250

1360

0.6

12000

Notes:

1. The outside dimension of the product with high voltage of 20kv shall be decided by both the buyer and seller.

2. The dimension in the table is for reference. The installation and design shall be subject to the outside dimension stated in the contract of our company.

Insulation level of product

Voltage class

kV

Effective value of the highest voltage of the equipment

kV

Effective value of rated short-duration power frequency withstand voltage

kV/min

Full-wave peak value of rated lightning impulse withstand voltage

kV

≤1

≤1.1

5

/

6

7.2

25

75

10

12

35

95

20

24

50

120

Pad mounted Transformers

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.