Product Detail
1.3 phases UPS power source, 2.100KVA, 3.High frequency, 4.With external battery bank, 5.EPO and Bypass.

KEY FEATURES:

Online double conversion VFI provide pure sine ware UPS power source.IGBT inverter and output isolation transformer improve the system efficiency and reliability for kinds of load: transformer, emergency light, electric facility, industry processes, etc.Parallel redundant, parallel up to 8 modules.Detect all the information and status showing on LCD.Intelligent RS232 Communication Port.Set output voltage from 220~240V.Over voltage, low voltage, over current, over load, etc can be detected and supply reliable protection. (EN/IEC60240).Advanced battery management.UPS monitoring software.

 Technical Parameters:

ModelHP10000
Capacity100KVA
Output power factor100~70%
Efficiency(normal operating), load 100%93~95%
Efficiency(economic model ), load 100%98%
Maximum leakage(mA)100
Mean time between failures(MTBF)200,000 hours
Remote signaling3 dry contact (battery low, battery discharge, bypass/failure);output 12Vdc 80mA
Remote controlEPO, bypass.
CommunicationRS232/C
Operating temperature0±40°C
Max relative humidity95%(non condensation)
Cool downMandatory wind( RPM change according to load.)
Altitude1KM output normal power( with increase of 100m, reduce 1%) Max 4KM
Noise60~65 dB
Protecting Standard(EN 60529)IP20
Incoming/outgoing cablesDownward/Back
StandardStandard:GB4943; Battery combinations:GB7260.2, GB/T 17626.2~5
Dimensions(W*D*H)mm1200*740*1400
Weight(without battery)KG900
Rectifier input(standard UPS) 
Rated voltage380V,3 phases
Voltage range±20%
Rated frequency50/60Hz auto sensing
Frequency range45~65
Maximum input current[A]175
Power Factor80%
Soft start0-100%,10 seconds
Battery 
Charge current setting0.5A*C10
Units(Rated voltage )216(432VDC)
Charge current setting0.2A*C10
Inverter output 
Rated voltage[v]380(3 phase+N)
Rated current[A]148
Phase voltage200~244V(control pannel)
WaveformSine wave
(Ipeak/Lrms) 
Linear load wave distortion<2%
Nonlinear load wave distortion<5%
Voltage Stability±1%
Transient voltage stability±5%(in 10ms)
Rated FrequencySame as input frequency.
Overload 600'/10'/1', (110/125/150% at nominal current.)
Inverter Efficiency96%
Bypass 
Rated Voltage380 (3 phase +N)
Input voltage range±15% (Settled to ±10% or ±25% via control panel available.)
Rated  Frequency50Hz/60Hz
Frequency range±2% (Settled to ±5% via control panel available.)
Inverter/bypass transfer time<1ms
Overload capacity10"/1"/18"(150/175/200% at nominal current.)