Key features:
1.True online double conversion technology
2.Wide input voltage range
3.Zero transfer time
4.Protection against all types of power problems
5.No add-on CNTL unit required for parallel connection
6.Low initial investment and flexible for future expansion
7.Highest reliability and maximum performance for power sharing and redundancy
8.Equipped with maintenance bypass switch
The best charger is designed to recharge low battery as quickly as possible with out damaging batteries in 2 amp up to 8 amp and 240VDC. Allowing 90% recharge in as little as 10 hours after a total drain.
a).Audible and visual over-load indicatorThe incorporated LED over load indicator prevents ups overloads and premature failure of the UPS. b).N+1 parallel redundancyAllows a 6 KVA to grow up to 18KVA or 12KVA with 6KVA redundancy, allowing user to add capacity as needed and lower investment. c).Simplified board separationDependent on the units all operation are separated into 5 PCBs allowing quick respond to damages and provides our valued dealers with simplified inventory and faster service to the end users. d).Dynamic bypassAutomatic dynamic bypass and manual bypass provide a loop to repair UPS with out having to disconnect loads ideal for non stop computing for critical applications. e).SNMP slotProvides remote monitoring and control of UPS where a PC is not present or where this function is needed to be separated. f)AS 400 dry contact cardOptional card to communicate in AS 400 protocols g).Sine-wave outputTrue sine-wave output with a 3% THD on batteries. This feature provides dependable and compatible power for your most critical applications. h).True double conversion technology with zero transfer timeThis advance design provides the closest you can get to pure constant power in the industry.
Technical specifications:
Model | H6KS/H6KL | H10KS/H10KL | |
Rated power | VA/W | 6KVA/4.2KW | 10KVA/7KW |
Input | Nominal voltage | 220VAC | |
Voltage range | 176~276VAC | ||
Frequency range | 46~54Hz | ||
Power factor | 0.98 | ||
Connection | Hardwired | ||
Output | Voltage | 220VAC±1% | |
Frequency | 50Hz±0.1%(battery mode) | ||
Waveform | Pure sine wave | ||
Power factor | 0.8 | ||
Voltage distortion | 2% under linear load | ||
Overload capability | 105%~130% for 10 min., ³130% for 1 min. | ||
Current crest ratio | 3:1 Max. | ||
Connection | Hardwired | ||
Battery | Type | Sealed, maintenance free, lead-acid | |
Quantity | 20 pieces | ||
Back-up time(full load) | 7 min | 5 min | |
Recharge time | 8 hrs to 90% of capacity after full load discharge | ||
Transfer time | 0ms | ||
Maintenance bypass switch | Yes | ||
LED indicators | Status | Load level/battery level, battery, utility power, inverter, bypass, overload, fault | |
Audible alarm | Bypass | Alarm beeps every two minutes | |
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||
Overload | Alarm beeps two for every second | ||
Fault | Alarm beeps continuously | ||
Acoustic noise | At 1 meter distance | £55 dB | |
Communication | DB-9 port | RS232 serial interface | |
Intelligent slot | Options: WebPower, AS400 or WinPower CMC | ||
Parallel port | Up to three units in parallel for power redundancy and load sharing | ||
Environmental | Operating temperature | 0~40°C | |
Operating humidity | 20%~90% non-condensing | ||
Weight | Net(Kg) | 35/84 | 38/93 |
Dimension | WxDxH(mm) | 260x570x717 |
High Frequency Online UPS 6KVA