Welcome to ECVERY
Online UPS Memo plus 1KVA-3KVA
Online UPS Memo plus 1KVA-3KVA
Supplier Info
[China Supplier]
Contact Person : Ms. Xiang Rita
Tel : 86-755-86169858
Fax : 86-755-86168482
Product Detail
1kva-3kva on-line ups; Output power factor up to 0.9. Three segment charging mode to increase battery service life,
MODELMP S 1KMP S 2KMP S 3K
CAPACITYVA/W1000VA/900W2000VA/1800W3000VA/2700W
INPUTVoltage Range200-290VAC at full load
Frequency Range45-55Hz at 50Hz/55-65Hz at 60Hz(auto-detect)
PhaseSingle phase with ground
Current THDI<7%(100% nonlinear load)<7%(100% nonlinear load)<7%(100% nonlinear load)
Power Factor>=0.98
Generator InputSupport
breaker7A16A25A
Input SocketIEC320 C13-10AIEC320 C20-16AIEC320 C20-16A
AC power cordIEC320 C14-10AIEC320 C19-16AIEC320 C19-16A
OUTPUTVoltage200/208/220/230/240VAC
Power Factor0.9
Voltage Regulation±2%
Frequency (Line Mode)46-54Hz at 50Hz/56-64Hz at60Hz
Frequency(Battery Mode)50/60Hz±0.02Hz
Current Crest Ratio3:1
Harmonic Distortion<=3% THD(Linear Load)
<=5% THD(Non-Linear Load)
Output WaveformPure Sinewave
Outlet(IEC C13-10A)*3(IEC C13-10A)*8(IEC C13-10A)*8 (IEC C19-16A)*1 
Overload CapacityLine Mode30S at 100%-150% ;300ms at >150%
Battery Mode30S at 100%-150% ;300ms at >150%
EFFICIENCYAC ModeFull load>=89%Full load>=89%Full load>=89%
Battery ModeFull load>=84%
ECO ModeFull load>=94%
BATTERYNumber of Batteries Per Set366
Battery Type12V/7Ah/9Ah12V/7Ah/9Ah12V/9Ah
Backup TimeEstimated remaining time displayed on the LCD
Recharge Time(to 90%)5 Hours5 Hours5 Hours
Charging Current(Max)1.0A1.0A1.0A
Rated Battery Voltage36Vdc72Vdc72Vdc
charge mode3-stage charging
ProtectOver-voltage /Over-current /Low-voltage
Battery SocketAnderson like PowerPole Modular Connectors
TRANSFER   TIMEMains ←→Battery0ms
Mains ←→ Bypass<4ms
OPTIONAL FEATURESEconomic Mode(ECO Mode)Support
INDICATORLCD Version(with LED)Load/Battery/Input/Output/Operating Mode Information
AUDIBLE ALARMBattery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinuously Sounding
PHYSICALDimension(W*D*H)mm144*409*215199*466*337
Net Weight(kg)1324.625.5
ENVIRONMENTSafetyCB
Operating Environment0-40ºC
Relative Humidity0-90%(non-condensing)
Altitude<1500m. when >1500m, derating
Noise Level<55dB at 1Meter
INTERFACESmart RS-232/USB(Preferential)Software supports Windows Family,Linus,FreeBSD
Intelligent SlotSNMP(independent to RS232)
* If rated input voltage select to be 200V , the low limit is 180V. If rated input voltage select to be 208V , the low limit is 190V. Under other condition the low limit is 200V.

MEMOPOWER PLUS SERIES

1-3KVA  1:1 PHASE (PF0.9)

 FEATURE:

Output power factor up to 0.9.

Three segment charging mode to increase battery service life, optimize recharge time.

Selectable High Efficiency mode of operation.

Cold start function to startup the UPS without utility.

Standard communication options: one RS-232 communication port, one USB communication port, and relay output contacts or SNMP card.

Power Shedding function may turn off uncritical load in battery backup to make longer backup time for critical load.

Extended runtime with up to four Extended Battery Modules (EBPs) per UPS.

Emergency shutdown control through the Remote Emergency Power-off (EPO) port.

Versatile LCD display with setting function.

Online UPS Memo plus 1KVA-3KVA

Ads by Google

About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.