Model | BUD220 -3050 | BUD220 -3100 | BUD220 -3150 | BUD220 -3300 | BUD220 -3500 | BUD220 -31000 | BUD220 -32000 |
DC input | Input rating voltage (VDC ) | 220 |
Input rating current (A) | 25.3 | 49.4 | 74 | 148 | 247 | 494 | 988 |
Input DC voltage allowing range (VDC ) | 180 ~ 300 |
AC input | Rating AC input voltage(VAC ) | 220( single-phase ) | 380 (three phase four wires) |
AC voltage allowing range( VAC ) | 220 ± 15% | 380 ± 15% |
Input AC allowing frequency ( Hz ) | 45 ~ 60 |
Power factor (PF) | 0.9 |
Bypass input | Allowing input voltage range(VAC ) | 380 ± 15% (three phase four wires) |
Input rating current(A) | 7.6 | 15.2 | 22.8 | 45.6 | 76 | 152 | 304 |
AC output | Rating capacity (KVA) | 5 | 10 | 15 | 30 | 50 | 100 | 200 |
Output rating power (KW) | 4 | 8 | 12 | 24 | 40 | 80 | 160 |
Output rating voltage and frequency | 380VAC , 50Hz (three phase four wires) |
Output rating current (A) | 7.6 | 15.2 | 22.8 | 45.6 | 76 | 152 | 304 |
Output voltage precision (V) | 380 ± 3% |
Output frequency precision (Hz) | 50 ± 0.05 |
Waveform deviation factor (THD) ( liner load ) | ≤ 5% |
Three-phase load unbalance ability | ≤ 100% |
Dynamic response ( load 0 ←→ 100%) | 5% |
Power factor (PF) | 0.8 |
Load ability | 150%,10 seconds |
Crest factor (CF) | 3:1 |
Inverted efficiency (80% resistance load ) | 92% |
Switchtime(ms) | AC DC screen | 0 |