AMF Control Panel
HGM6320T automatic control module is specially designed for mobile communication base station, whose functions can be configured according to actual using of the station. It can not only control types of generators automatically, but can monitor temperature of engine room and battery voltage to control mains/load, and mains/double ATS switch. When alarm occurs, it can inform the servicing staff by sending short message.
HGM6320T controller adopts large liquid crystal display (LCD) and selectable Chinese and English interface with compact structure, advanced circuits, simple connections and high reliability.
Performance and characteristics Microprocessor control, big screen LCD with back-lit display, selectable Chinese and English interface, touch button operation; Precise measure and display function: almost can monitor all the related electricity parameter and water temperature, oil pressure, fuel level and so on;Main monitoring items:
Mains 3 /single phase voltage
Gens 3 /single phase voltage
Load 3 /single phase current
Mains Frequency
Gens Frequency
Engine rotating speed
Engine rotating temperature
Oil pressure
Fuel level
Room temperature
Battery voltage
Specification
Item | Content |
Working Voltage | DC8. 0V to 35. 0V, Continuous Power Supply |
Power Consumption | <3W(Standby mode: ≤2W) |
Alternator Input Range 3-Phase 4 Wire 3-Phase 3 Wire Single-Phase 2 Wire 2-Phase 3 Wire | 15V AC - 360 VAC (ph-N) 30V AC - 600 VAC (ph- ph) 15V AC - 360 VAC (ph-N) 15V AC - 360 VAC (ph-N) |
Alternator Input Frequency | 50Hz /60Hz |
Magnetic Volt Input Range | 1.0V to 24.0V (RMS) |
Magnetic Input Frequency | 10,000 Hz (max) |
Start Relay Output | 16 Amp DC28V at DC supply output. |
Fuel Relay Output | 16 Amp DC28V at DC supply output. |
Auxiliary Relay Output (1-3) | 16Amp DC28V at DC supply output. |
Auxiliary Relay Output (4-6) | 16Amp 250VAC passive output. |
Battery Voltage Range | (0-100)VDC |
Ambient Temperature | (0-50)ºC |
Overall Dimensions | 240mm x 172mm x 57mm |
Panel Cutout | 214mm x 160mm |
C. T. Secondary | 5A (rated) |
Working Condition | Temperature: (-25~70)°C Humidity: (20~90)% |
Storage Condition | Temperature: (-30~+80)°C |
Protection Level | IP55: when with waterproof rubber ring added between controller and its panel. IP42: when without waterproof rubber ring between controller and its panel. |
Insulation Intensity | Object: between input/output/power Quote standard: IEC688-1992 Test way: AC1.5 kV/1min 2mA leakage current |
Weight | 0.90kg |